FAQ - Power DBX 2000 & DIB 2000 Hydrogen UPS system
| ||||||
|
When the FC is running, LED 3 & 4 are green and LED 2 is showing the H2 situation (yellow means low on hydrogen and ‘light off’ is OK). This is different from standby state. In standby state LED 1 would be green also. |
| ||||||
|
This data is saved in the log. The log can be read, either via TCI/IP, CANbus or it can be read on the internal memory which is stored on a removable SD-card. |
| ||||||
|
The system would go into backup mode, exactly in the same way as if the system was in standby mode when the outage happend. |
| ||||||
|
It is set from the day it passes FAT or when a technician during commissioning runs a self test. |
| ||||||
|
Either a 30 days period since the last fuel cell startup or pushing the self test button. |
| ||||||
|
Yes, it is the same, but at the same time it is the button that would allow a technician to get the system out of one of the ‘safe modes’. The safe modes are controlled shutdowns of the system in case of malfunction. |
| ||||||
|
Yes, if the outage has lasted more than 1 second. |
| ||||||
|
They would self test after 30 days from an outage, so they could test at the same time. This is depending on the type of outage though. Otherwise they would test randomly depending on the time of commissioning. |